1. Connection
The Aidoo Wi-Fi Controller has a terminal for connection and integration via Modbus.
For proper operation of the system, verify that only the communication cables (green-blue) are connected.
2. Add a new unit / Associate with Aidoo
Associate your Aidoo by following the instructions described in the section Add a unit/zone, remember that you must indicate the Modbus port to which the Aidoo must point within Webserver information.
3. Registers
Consult the available records:
Nº | Description | Values | Operations |
---|---|---|---|
0 | On/Off | 0: Off; 1: On | 0x03, 0x04, 0x06, 0x10, 0x16 |
1 | Setpoint | Setpoint x 10; Example: 22.5 ˚C = 225 | 0x03, 0x04, 0x06, 0x10, 0x16 |
2 | Room temperature (Localtemp) | Localtemp x 10; Example: 22.5 ˚C = 225 | 0x03, 0x04 |
3 | Operations modes (Modes) | 1: Auto, 2: Cooling, 3: Heating, 4: Fan, 5: Dry | 0x03, 0x04, 0x06, 0x10, 0x16 |
4 | Speeds | 0: Auto, X: SX (X: 1 - 7) | 0x03, 0x04, 0x06, 0x10, 0x16 |
5 | Louvers | X: Position X | 0x03, 0x04, 0x06, 0x10, 0x16 |
6 | Warnings | Indoor unit warning code (max 2 bytes) | 0x03, 0x04 |
7 | Errors | Indoor unit error code (max 2 bytes) | 0x03, 0x04 |
For more information, please refer to the Aidoo Modbus integration manual.