1. Connection

The Aidoo Wi-Fi Controller has a terminal for connection and integration via Modbus.

For proper operation of the system, verify that only the communication cables (green-blue) are connected.

Connection Modbus

2. Add a new unit / Associate with Aidoo

Associate your Aidoo by following the instructions described in the section Add a unit/zone, remember that you must indicate the Modbus port to which the Aidoo must point within Webserver information.

Add unit - modbus

3. Registers

Consult the available records:

Description Values Operations
0 On/Off 0: Off; 1: On 0x03, 0x04, 0x06, 0x10, 0x16
1 Setpoint Setpoint x 10; Example: 22.5 ˚C = 225 0x03, 0x04, 0x06, 0x10, 0x16
2 Room temperature (Localtemp) Localtemp x 10; Example: 22.5 ˚C = 225 0x03, 0x04
3 Operations modes (Modes) 1: Auto, 2: Cooling, 3: Heating, 4: Fan, 5: Dry 0x03, 0x04, 0x06, 0x10, 0x16
4 Speeds 0: Auto, X: SX (X: 1 - 7) 0x03, 0x04, 0x06, 0x10, 0x16
5 Louvers X: Position X 0x03, 0x04, 0x06, 0x10, 0x16
6 Warnings Indoor unit warning code (max 2 bytes) 0x03, 0x04
7 Errors Indoor unit error code (max 2 bytes) 0x03, 0x04

For more information, please refer to the Aidoo Modbus integration manual.